Energy-saving air conditioning systems

Cover Page

Cite item

Full Text

Abstract

The unitary-central air-conditioning system for the shop of production electronic equipment is considered as an example of energy-saving air conditioning system. The incoming outside air is prepared in the central, conditioner in compliance with sanitary standards on the quantity a moisture absorption. Tn the unitary fan air conditioners the air from the cent air conditioner is mixed with the cooled inside air and comes into the work zone with the temperature as selected according to conditions of comfort, j modes of operation of the unitary-central air-conditioning system in win and summer period are considered. The advantages of the described a conditioning system are presented in comparison to the central one.

About the authors

O. Ya. Kokorin

Moscow State Construction University

Author for correspondence.
Email: info@eco-vector.com

Doctor of Technical Sciences, Professor

Russian Federation, Moscow

V. V. Komissarov

ZAO Venta

Email: info@eco-vector.com
Russian Federation

References

Supplementary files

Supplementary Files
Action
1. JATS XML
2. Fig. 1. Construction on the I-d-diagram of the year-round modes of operation of the local-central ACS in the climate of Moscow.

Download (1MB)
3. Fig. 2. Schematic diagram of the central air conditioner for year-round preparation of supply outside air: 1 - air multi-valve; 2 - filter; 3 - heat exchanger of exhaust air heat recovery unit with pump circulation of antifreeze; 4 - calorifer with regulation unit; 5 - air cooler with regulation unit; 6 - adiabatic humidifying unit; 7 - supply fan; 8 - supply air duct to local fan units; 9 - temperature control sensor of prepared air by wet thermometer tох.м; 10 - microprocessor controller

Download (1MB)
4. Fig. 3. Schematic diagram of a local fan unit in the shop to maintain the required indoor air temperature in several process areas: 1 - air valve with manual drive of setting control of indoor air intake Lv.ox; 2 - filter; 3 - air cooler with control unit; 4 - air valve with manual drive of setting control of air intake from the central air conditioner; 5 - supply air duct from the central air conditioner (see Fig. Fig. 2); 6 - mixing chamber; 7 - supply fan; 8 - local supply air duct; 9 - laminar air distributor of supply air Ln in the working area; 10 - sensor controlling air temperature tv in the working area