A Possibility of Reducing the Induced Voltage Within a Repair Area1


Citar

Texto integral

Acesso aberto Acesso aberto
Acesso é fechado Acesso está concedido
Acesso é fechado Somente assinantes

Resumo

The electromagnetic effect of a live high-voltage line on a disconnected line is analyzed. It is shown by calculation that the zero-potential point of the disabled conductor can be shifted to the repair area by changing the grounding resistance at the substations. To this end, adjustable resistors placed between the disabled conductor and the grounding devices at the substations can be used. The possibility of automating this process is examined.

Sobre autores

A. Monakhov

National Research University “Moscow Power Engineering Institute”

Autor responsável pela correspondência
Email: a-monakhov@yandex.ru
Rússia, Moscow

E. Degtyarenko

National Research University “Moscow Power Engineering Institute”

Email: a-monakhov@yandex.ru
Rússia, Moscow

D. Danilov

National Research University “Moscow Power Engineering Institute”

Email: a-monakhov@yandex.ru
Rússia, Moscow

Arquivos suplementares

Arquivos suplementares
Ação
1. JATS XML

Declaração de direitos autorais © Springer Science+Business Media New York, 2016